NTIS 바로가기전기학회논문지 = The Transactions of the Korean Institute of Electrical Engineers, v.66 no.9, 2017년, pp.1309 - 1316
오윤식 (Dept. of Information and Communication Engineering, Sungkyunkwan University) , 조규정 (Dept. of Information and Communication Engineering, Sungkyunkwan University) , 김민성 (Dept. of Information and Communication Engineering, Sungkyunkwan University) , 김지수 (Dept. of Information and Communication Engineering, Sungkyunkwan University) , 김철환 (Dept. of Information and Communication Engineering, Sungkyunkwan University)
As penetration level of Distributed Generations (DGs) on weak distribution networks gets higher, voltage rise problem can often occur due to reverse power which is not expected in conventional distribution networks. It, however, cannot be effectively solved by using conventional voltage regulating d...
* AI 자동 식별 결과로 적합하지 않은 문장이 있을 수 있으니, 이용에 유의하시기 바랍니다.
핵심어 | 질문 | 논문에서 추출한 답변 |
---|---|---|
분산전원에서 기존기기들과의 협조 제어를 이용한 새로운 전압조정 방식 개발은 왜 필요한가? | 하지만 기상 조건에 의해 쉽게 영향을 받을 수 있는 풍력 발전 및 태양광 발전의 간헐적인 출력 특성으로 인해 On-load Tap Changer (OLTC), Step Voltage Regulator (SVR), 커패시터 뱅크 등과 같은 종래의 전압조정 기기들의 효율적인 동작을 더 이상 기대하기 어려운 실정이다[5-6]. 계통 연계용 인버터의 출력 제어를 통한 분산전원의 전압조정 참여가 하나의 대안이 될 수 있지만, 기존 전압조정 기기들과의 협조 제어가 수립되지 않는다면 과도한 조정 동작 등의 문제를 야기할 수 있다. 따라서 기존기기들과의 협조 제어를 이용한 새로운 전압조정 방식 개발이 필요하다. | |
전압변동에 영향을 주는 요소는 무엇인가? | 식 (1)을 통해 알 수 있듯이, 종래의 배전계통의 전압변동은 단방향 조류 특성으로 인해 항상 전압강하(ΔV 는 +의 값을 가짐)의 형태로 나타난다. 또한, 전압변동은 선로의 등가임피던스(R, X) 및 선로를 통해 공급되는 부하의 유효(P) 및 무효전력(Q)에 의해 크게 영향을 받는다. 즉, 선로가 길어지고 수전단에 위치한 부하의 크기가 증가할수록 배전계통의 전압강하 현상이 크게 발생한다. | |
분산전원의 배전계통 연계를 가로막는 장애물은 무엇인가? | 화석연료의 높은 사용량으로 인해 기후 변화 및 지구온난화의 영향이 직접적으로 인류에게 미치기 시작함에 따라 화석연료의사용량을 줄임과 동시에 신재생에너지를 이용한 분산전원(Distributed Generation, DG)의 설치 및 이용에 대한 관심이 전 세계적으로 고조되고 있으며, 특히 배전계통에 신재생에너지인 풍력 발전, 태양광 발전 및 소형 열병합 발전 등 중소규모 전원을 분산 배치하는 분산전원 도입이 점점 증가하고 있는 추세이다[1-2]. 이러한 분산전원의 배전계통 연계는 계속해서 증가할 것으로 예상되지만 현재의 배전계통 인프라와 운영방식에서 대용량분산전원을 수용하기 위해서는 한계가 존재하며, 발생 가능한 기술적 문제로는 규정전압 이탈, 보호협조 저해, 단락용량 증대, 전기품질 저하, 단독운전에 의한 계통운영의 안전성 저하 등을 예로 들 수 있다[3-4]. |
CIGRE WG B5.34, The Impact of Renewable Energy Sources and Distributed Generation on Substation Protection and Automation, August 2010
Brahma S, Girgis A., "Microprocessor-based reclosing to coordinate fuse and recloser in a system with high penetration of distributed generation," IEEE power engineering society winter meeting, 2002
CIGRE WG B5/C6.26/CIRED, Protection of Distribution Systems with Distributed Energy Resources, March 2015.
I. Xyngi, A. Ishchenko, M. Popov, L. Van der Sluis, "Transient Stability Analysis of a Distribution Network With Distributed Generators," IEEE Transactions on Power Systems, vol. 24, no. 2, pp.1102-1104, May 2009.
D. Ranamuka, A. P. Agalgaonkar, K. M. Muttaqi, "Online Voltage Control in Distribution Systems with Multiple Voltage Regulating Devices," IEEE Transactionson Sustainable Energy, vol. 5, no. 2, pp. 617-628, 2014.
Xiaohu Liu, A. Aichhorn, L. Liu, H. Li, "Coordinated Control of Distributed Energy Storage System with Tap Changer Transformers for Voltage Rise Mitigation under High Photovoltaic Penetration," IEEE Transactions on Smart Grid, vol. 3, no. 2, pp. 897-906, 2012.
M. A. Mahmud, M. J. Hossain, H. R. Pota, "Analysis of Voltage Rise Effect on Distribution Network with Distributed Generation," The 18th IFAC World Congress, vol. 44, iss. 1, pp. 14796-14801, 2011.
E. M. Lee et al., "A Study on the Optimal Introduction of Step Voltage Regulator(SVR) in Distribution Feeders" The Transactions of the KIEE, vol. 53A, no. 11, pp. 610-618, 2004.
Yasuhiro hayashi, "Determination of Optimal Sending Voltage Profile in Distribution Systems with Distributed Generators", Electrical Engineering in Japan, Vol. 161, No. 2, 2007
IEEE Std. 1547.2, IEEE Standard for Interconnecting Distributed Resources with Electric Power Systems, 2008.
EPRI, Common Functions for Smart Inverters, Version 3, Feb. 2014.
C. Kang, H. S. Shin, J. F. Moon, G. H. Choe, J. C. Kim, "An Improved Voltage Regulation Method in Power Distribution System Interconnected Multiple PV Systems," Journal of KIIEE, vol. 23, no. 2, pp. 53-61, 2009.
S. Conti, S. Raiti, G. Vagliasindi, "Voltage Sensitivity Analysis in Radial MV Distribution Networks using Constant Current Models," in Proc. IEEE Int. Symp. Ind. Electron, 2010.
Y. S. Oh et al., "Modeling of Practical Photovoltaic Generation System using Controllable Current Source based Inverter", The Transactions of the KIEE, vol. 65, no. 8, pp. 1340-1346, 2016.
*원문 PDF 파일 및 링크정보가 존재하지 않을 경우 KISTI DDS 시스템에서 제공하는 원문복사서비스를 사용할 수 있습니다.