Watertight 25.8 kV/600 A/12.5 kA fault current limiters (FCLs) have successfully installed in five areas (Incheon, Seoul, Gyeong-gi, Daejeon, Suwon) on KEPCO power distribution line for the purpose of commercial demonstrations. The fault current limiting operation of this FCL, which includes functio...
Watertight 25.8 kV/600 A/12.5 kA fault current limiters (FCLs) have successfully installed in five areas (Incheon, Seoul, Gyeong-gi, Daejeon, Suwon) on KEPCO power distribution line for the purpose of commercial demonstrations. The fault current limiting operation of this FCL, which includes functions of sensing, commutation, and reduction of fault currents, is perfectly completed within 1 cycle immediately after fault occurs. The performance of FCL was verified by short circuit test, impedance test, insulation test, temperature-rise test, and control test, etc at PT&T in LS industrial systems, which is the official certification institute in Korea. In 2013, and also the FCL field test was performed in order to test the protection coordination between conventional relays and FCL, on the 1.5 kA and 5.0 kA faults, which were made by connecting the Artificial Fault Generator (AFG) to the distribution line in test grid at KEPCO Power Testing Center. The next step of this project is to check the FCL conditions caused by real external environment, and acquire the various data from five regions installed with FCL. In this paper, we intend to explain the FCL specifications and performance characteristics, and check the expected effect by application of FCL to power distribution line based on the power system analysis of an application site.
Watertight 25.8 kV/600 A/12.5 kA fault current limiters (FCLs) have successfully installed in five areas (Incheon, Seoul, Gyeong-gi, Daejeon, Suwon) on KEPCO power distribution line for the purpose of commercial demonstrations. The fault current limiting operation of this FCL, which includes functions of sensing, commutation, and reduction of fault currents, is perfectly completed within 1 cycle immediately after fault occurs. The performance of FCL was verified by short circuit test, impedance test, insulation test, temperature-rise test, and control test, etc at PT&T in LS industrial systems, which is the official certification institute in Korea. In 2013, and also the FCL field test was performed in order to test the protection coordination between conventional relays and FCL, on the 1.5 kA and 5.0 kA faults, which were made by connecting the Artificial Fault Generator (AFG) to the distribution line in test grid at KEPCO Power Testing Center. The next step of this project is to check the FCL conditions caused by real external environment, and acquire the various data from five regions installed with FCL. In this paper, we intend to explain the FCL specifications and performance characteristics, and check the expected effect by application of FCL to power distribution line based on the power system analysis of an application site.
* AI 자동 식별 결과로 적합하지 않은 문장이 있을 수 있으니, 이용에 유의하시기 바랍니다.
문제 정의
8kV 지중선로용 한류기의 개발 및 한전 시범사용 규격 제정, 인증 기관 시험 및 필드 테스트가 완료되고, 한전 실계통 5개소에 한류기 설치가 완료됨에 따라 한류기의 상용화가 점점 현실화 되고 있다. 본 논문에서는 한류기의 동작 원리 및 정격을 이해하고, 설치 계통 분석을 통해 한류기 적용으로 인한 기대효과를 검토하였다. 5개소에 설치된 한류기의 실계통 운전을 통해 외부 환경에 따른 침수, 온도상승, 결로 발생 등 운영실태 및 개선사항 여부를 점검할 계획이다.
본 논문에서는 한전 선로에 설치된 한류기 개발 사양 및 기본 성능을 이해하고, 한류기 설치 계통의 분석을 통해 한류기 적용시 기대효과를 구체적으로 검토해 보고자 한다.
9kV-Y), 정격전류 600A 이하의 교류회로에 적용되는 옥외용 한류기로 표 1에 정격이 정리되어 있다. 한전 계통 중 고장 발생 빈도가 높은 지역의 변전소와 다회로 차단기 사이에 설치된 한류기는 고장 전류 저감과 차단기와의 보호협조를 통해 정전구간을 최소화하는 것이 목적이다.
제안 방법
순시탭은 50과 45로 셋팅되어 있고, CT 비는 600 : 5 이다. 다회로 차단기의 한시커브는 N3 한전 곡선으로 단락과 지락 고장에 대해서 최소동작전류를 400A, 70A로 설정하였고, 대전류 개방 동작전류는 각각 3,500A, 1,750A로 설정하였다. 이러한 계통에서의 한류기 미설치 또는 설치시의 보호협조를 다음과 같이 검토 할 수 있다.
성능/효과
5 kA 한류기는 지중배전선로의 보호협조 구현을 통한 계통 정전 구간(또는 시간) 최소화와 신속한 고장전류 저감을 통한 선로의 기계적 열적 스트레스 경감을 목적으로 개발되었다. 또한 한류기의 한전 시범사용 규격 제정 및 한국전기연구원(KERI)에서의 규격시험이 완료 되었고, 고창 한전 시험 선로에서의 AFG를 이용한 필드 테스트(인위적 고장전류 발생을 통한 한류기 성능 구현)를 통해 한류기의 효과가 입증되었다. 최근에는 한전 5개 사업소(인천, 서울, 경기, 대전충남, 남서울 본부)에 한류기를 설치 완료 하였고, 약 1여년간의 운전을 통해 고장 발생에 대한 한류기의 기능 구현 뿐 만 아니라 외부 환경에 따른 침수, 온도상승, 결로 발생 등 운영실태 및 개선사항 여부를 점검할 계획이다.
후속연구
본 논문에서는 한류기의 동작 원리 및 정격을 이해하고, 설치 계통 분석을 통해 한류기 적용으로 인한 기대효과를 검토하였다. 5개소에 설치된 한류기의 실계통 운전을 통해 외부 환경에 따른 침수, 온도상승, 결로 발생 등 운영실태 및 개선사항 여부를 점검할 계획이다.
또한 한류기의 한전 시범사용 규격 제정 및 한국전기연구원(KERI)에서의 규격시험이 완료 되었고, 고창 한전 시험 선로에서의 AFG를 이용한 필드 테스트(인위적 고장전류 발생을 통한 한류기 성능 구현)를 통해 한류기의 효과가 입증되었다. 최근에는 한전 5개 사업소(인천, 서울, 경기, 대전충남, 남서울 본부)에 한류기를 설치 완료 하였고, 약 1여년간의 운전을 통해 고장 발생에 대한 한류기의 기능 구현 뿐 만 아니라 외부 환경에 따른 침수, 온도상승, 결로 발생 등 운영실태 및 개선사항 여부를 점검할 계획이다.